Coordinative performance of HVDC circuit breakers in MTDC grids

Conference Paper (2020)
Author(s)

Siyuan Liu (TU Delft - Electrical Engineering, Mathematics and Computer Science, Xi’an Jiaotong University)

Ajay Shetgaonkar (TU Delft - Electrical Engineering, Mathematics and Computer Science)

Marjan Popov (TU Delft - Electrical Engineering, Mathematics and Computer Science)

Research Group
Intelligent Electrical Power Grids
DOI related publication
https://doi.org/10.1109/PESGM41954.2020.9281921 Final published version
More Info
expand_more
Publication Year
2020
Language
English
Research Group
Intelligent Electrical Power Grids
Bibliographical Note
Green Open Access added to TU Delft Institutional Repository ‘You share, we take care!’ – Taverne project https://www.openaccess.nl/en/you-share-we-take-care Otherwise as indicated in the copyright section: the publisher is the copyright holder of this work and the author uses the Dutch legislation to make this work public.
Article number
9281921
Pages (from-to)
1-5
Publisher
IEEE
ISBN (print)
978-1-7281-5509-8
ISBN (electronic)
978-1-7281-5508-1
Event
2020 IEEE Power and Energy Society General Meeting (PESGM) (2020-08-02 - 2020-08-06), Montreal, Canada
Page Views
444
Collections
Institutional Repository
Reuse Rights

Other than for strictly personal use, it is not permitted to download, forward or distribute the text or part of it, without the consent of the author(s) and/or copyright holder(s), unless the work is under an open content license such as Creative Commons.

Abstract

The objective of this paper is to investigate the coordinative performance of different types of high voltage DC (HVDC) circuit breakers (CBs) in multi-terminal DC (MTDC) grids. Several different HVDC CB technologies are emerging as a solution for the protection of offshore MTDC grids. There is a need for coordinative operation between different types of DC CBs in the same network. In this paper, two typical types of DC CBs are modelled in detail and implemented in a 4terminal MTDC grid in PSCAD environment, by considering operation time, interruption capability and interruption characteristics. Since the requirement of the DC CBs depends on the magnitude of the interrupted current where they are implemented, the fault scenarios in all terminals are studied and the worst scenarios are selected to demonstrate the coordinative performance of different DC CBs. Four cases are defined and demonstrated by two different types of CBs at each terminal of the cable. DC CBs perform differently with the change of the operating time and the locations where they are implemented. The performances and energy absorption are compared and analyzed. The obtained results can be used as DC CB’s selection optimization methodology for future MTDC grids.

Files

09281921.pdf
(pdf | 0.797 Mb)
- Embargo expired in 17-08-2021